Stamford Generator AVR- MX341
Brand |
Stamford
|
Model Name/Number |
Mx341
|
Phase |
Three Phase
|
Output Voltage |
Max 120V DC
|
Operating Temp. |
-40 to +70 Degree C
|
Sensing Input Voltage |
190-264V ac max, 1 phase, 2 wire
|
Sensing Input Frequency |
50-60 Hz nominal
|
Power Input Voltage |
140-220V ac max, 3 phase, 3 wire
|
Power Input Current |
3A/phase
|
Power Input Frequency |
100-120 Hz nominal
|
Output Current |
continuous 2.7 A Intermittent 6A for 10 secs.
|
Output Resistance |
15 ohms minimum
|
Regulation |
+/- 1% (see note 1)
|
Thermal Drift |
0.03% per o C change in AVR ambient (note 2)
|
Soft Start Ramp Time |
3 seconds
|
AVR Response |
10 ms
|
Filed current to 90% |
80 ms
|
Machine Volts to 97% |
300 ms
|
External Voltage Adjustment |
+/-10% with 1 k ohm 1 watt trimmer (see note 3)
|
Under Frequency Protection Set Point |
95% Hz (see note 4)
|
Under Frequency Protection Slope |
170% down to 30 Hz
|
Power Dissipation |
12 watts maximum
|
Maximum Input |
+/- 5V dc (see note 5)
|
Sensitivity |
1v for 5% Generator Volts (adjustable)
|
Input resistance |
1k ohm
|
Quadrature Droop Input |
10 ohms burden , Max. sensitivity: 0.07 A for 5% droop 0PF , Max. input: 0.33 A
|
Relative Humidity |
95%
|
Storage temperature |
Storage temperature -55 to +80 Degree C
|
The AVR senses the voltage in the main generatormwinding and controls the power fed to the exciter stator,and hence the main rotor to maintain the generator output voltage within the specified limits, compensating for load, speed, temperature and power factor of the generator.mSoft start circuitry is included to provide a smoothmcontrolled build up of generator output voltage.
A frequency measuring circuit continually monitors the shaft speed of the generator and provides under-speed protection of the excitation system by reducing the generator output voltage proportionally with speed below a pre-settable threshold. A further enhancement of this feature is an adjustable volts per Hertz slope to improve engine recovery time on turbo charged engines. Soft start circuitry is included to provide a smooth controlled build up of generator output voltage.
Uncontrolled excitation is limited to a safe period by internal shutdown of the AVR output device. This condition remains latched until the generator has stopped.
Provision is made for the connection of a remote voltage trimmer, allowing the user fine control of the generator’s output.
An analogue input is provided allowing connection to a STAMFORD Power Factor controller or other external devices with compatible output.
The AVR has the facility for droop CT connection, to allow parallel running with other similarly equipped generators.